The main factors affecting the adsorption performance of activated alumina:
① Particle size: The smaller the particle size, the higher the adsorption capacity, but the smaller the particle size, the lower the particle strength, which affects its service life.
② PH value of raw water: when the PH value is greater than 5, the lower the PH value, the higher the adsorption capacity of activated alumina.
③ Initial fluorine concentration of raw water: the higher the initial fluorine concentration, the larger the adsorption capacity.
④ Raw water alkalinity: The high concentration of bicarbonate in raw water will reduce the adsorption capacity.
⑤ Chloride and sulfate ions.
⑥ Influence of arsenic: activated alumina has an adsorption effect on arsenic in water.
The accumulation of arsenic on activated alumina causes a decrease in the adsorption capacity of fluoride ions, and it is difficult to elute arsenic ions during regeneration.